Description
The OPEN 600 EMS (Energy Management Station) is designed as a native BACnet controller. It supports the BACnet protocol acc. to the ANSI / ASHRAE standard with up to 250 BACnet objects. The OPEN 600 EMS is tested acc. to DIN EN 16484-6 and BTL/WSPLab Test Plan, certified to the rules by BACnet Interest Group Europe and BTL listed. It has got the AMEV attestation with B profile in the extended version. The OPEN 600 EMS is equipped with 32 integrated in- and outputs and can be extended with up to 5 additional IO modules accord. to the version. The OPEN 600 EMS can be ordered with and w/o manual control. It can be connected directly to the analog inputs sensors with the measurement elements 10mV/K, Pt1000, Ni1000 DIN and Ni1000 TK5000 as the analog inputs have integrated transducers. The OPEN 600 EMS supports up to 112 physical data points.
Technical Information
BACnet – functionalities The OPEN 600 EMS supports the BACnet Device Profile "BACnet Building Controller (B-BC)". It can be used concurrent as a BACnet Server, BACnet Client and BACnet Router. Following Data-LinkLayers can be used simultaneously: • BACnet / IP • BACnet MS/TP Master • BACnet PTP EIA 232 • BACnet PTP Modem Moreover it supports the functionality BACnet Broadcast Management Device (BBMD) incl. Foreign Device Registration for BACnet / IP. Detailed data for supported BACnet Objects and BACnet Services are given in the data sheet BACnet Implementation Conformance Statement (PICS).
Description
The OPEN 810 EMS (Energy Management Station) controller is designed as a native BACnet controller. It supports the BACnet protocol acc. to the ANSI/ASHRAE Standard with up to 1000 BACnet objects. The OPEN 810 EMS is tested acc. to DIN EN 16484-6 and BTL/WSPLab Test Plan, certified to the rules by BACnet Interest Group Europe and BTL listed. It has got the AMEV attestation with B profile in the extended version. The OPEN 810 EMS has one CAN interface. Three versions for connecting 5, 12 or 32 OPEN IO modules facilitate the use for different sized installations. The controller OPEN 810 EMS supports up to 512 physical data points.
Technical Information
BACnet – functionalities The OPEN 810 EMS supports the BACnet Device Profile "BACnet Building Controller (B-BC)". It can be used concurrent as a BACnet Server, BACnet Client and BACnet Router. The following Data-Link Layers can be used simultaneously: • BACnet / IP • BACnet MS/TP Master • BACnet PTP EIA 232 • BACnet PTP Modem Moreover it supports the functionality BACnet Broadcast Management Device (BBMD) incl. Foreign Device Registration for BACnet / IP. Detailed data for supported BACnet Objects and BACnet Services are given in the data sheet BACnet Implementation Conformance Statement (PICS).
Description Digital output module for mounting on 35 mm DIN rail. The 45 mm automat profile module is also suitable for the installation in distribution or control cabinets, etc.. Control via CAN-bus in combination with an OPEN EMS. • 8 transistor outputs, 24 V DC 80 mA • Short-circuit proof, electrically isolated • 8 LEDs for operating status • removable spring terminals up to 1.5 mm² • Supply voltage: 24 V DC • Current consumption: 50 mA, plus supply of connected units. • CAN-bus: CAN 2.0B, electrically isolated ISO 11898, Baud rate: 10 kbit/s .. 1 Mbit/s, preset to 50 kbit/s
CAUTION !! Free terminals must not be used as connecting terminals.
Note: